Power Quality

Real supply voltage isn't a perfect sine. Learn harmonics and THD, sags, swells, flicker, unbalance and transients, power-factor correction, harmonic resonance and filters, and the standards that limit them.

Sensitive electronics, variable-speed drives, LEDs and data centres all interact with the supply. Non-linear loads draw distorted currents, faults cause voltage dips, and switching causes transients. Power quality is about keeping voltage and current close enough to the ideal that equipment works and lasts.

Poor power quality costs industry dearly: drives trip on sags, capacitors fail from harmonics, transformers overheat, and neutral conductors overload.

An analogy

Clean power is like a calm, steady river. Harmonics are ripples, sags are sudden drops in level, and transients are waves from a passing boat — equipment built for a calm river can be swamped.

Common disturbances

Each disturbance has different causes and fixes.

Harmonics

Non-linear loads (rectifiers, drives, LED drivers, computers) draw current in pulses. Fourier analysis decomposes it into the fundamental plus harmonics at integer multiples. Six-pulse drives produce 5th, 7th, 11th, 13th…; single-phase rectifiers produce strong 3rd harmonics, which add up in the neutral of a four-wire system (triplen harmonics don't cancel).

Power-factor correction

Capacitor banks supply reactive power locally, reducing current, losses and utility penalties. Size them with Q_c = P(tan φ₁ − tan φ₂). Automatic banks switch steps as load varies to avoid over-correction and voltage rise.

Harmonic resonance

A capacitor bank in parallel with the network's inductance forms a resonant circuit at h_r ≈ √(S_sc/Q_c). If that falls near a harmonic the loads produce, the harmonic voltage is amplified and capacitors fail. The fix is a detuned bank: a series reactor (typically 7 %, tuned near 189 Hz on 50 Hz) moves resonance below the 5th harmonic.

Mitigation and standards

Passive tuned filters, active harmonic filters (inverters injecting cancelling currents), 12/18-pulse and active-front-end drives, UPS/DVR for sags, and surge protection devices. Standards: IEEE 519 (harmonic limits at the point of common coupling), IEC 61000-3-2/-3-12 (equipment emissions), EN 50160 (supply voltage characteristics).

Formulas

Worked example: THD and RMS current

Given: I₁ = 100 A; I₃ = 30 A, I₅ = 20 A, I₇ = 10 A

Find: THD and true RMS current.

Answer: THD = 37.4 %, I_rms = 106.8 A

Worked example: Capacitor bank for PF correction

Given: P = 100 kW; pf₁ = 0.70 → pf₂ = 0.95

Find: Required capacitor kvar.

Answer: ≈ 70 kvar

Common mistakes

Applications

Key takeaways

Going further