Fault Analysis

Short circuits drive currents many times normal load. Learn the per-unit system, symmetrical three-phase faults, fault MVA, DC offset, and unsymmetrical faults with symmetrical components — the basis for rating breakers and setting protection.

When insulation fails — a tree touches a line, a cable is dug up, lightning flashes over — current takes a low-impedance path and rises to tens of kiloamps. Equipment must withstand it and breakers must interrupt it within a few cycles.

Fault studies calculate those currents. They size switchgear, set protection relays, design earthing and check that equipment survives the mechanical and thermal stress.

An analogy

A short circuit is like a dam breach: normal flow is set by the turbines and channels (the load); a breach lets water rush through limited only by the dam's own opening (the source impedance).

Types of fault

Faults are classified by which conductors are involved.

The per-unit system

Expressing quantities as fractions of chosen base values makes transformer ratios disappear (a transformer's pu impedance is the same on both sides) and keeps numbers in a familiar range. Choose S_base once for the whole system and V_base in each voltage zone set by transformer ratios.

Fault level

S_sc = S_base / Z_pu (total pu impedance to the fault). A 20 MVA transformer with 10 % impedance fed from an infinite grid can supply at most 200 MVA into a fault on its secondary. Transformer impedance is the main thing limiting distribution fault levels.

DC offset and breaker duties

Because current in an inductive circuit can't change instantly, a fault starting at a voltage zero includes a decaying DC offset with time constant τ = X/(ωR). The first peak can reach ~2.5× the symmetrical RMS value. Breakers are rated for symmetrical breaking current and for peak making current.

Symmetrical components

An unbalanced three-phase set can be split into positive-, negative- and zero-sequence sets. Each sequence has its own network; the fault type decides how they connect: SLG puts all three in series. Zero-sequence current flows only if a path to earth exists, so transformer winding connections (Δ blocks zero sequence) and earthing strongly affect earth-fault currents.

Formulas

Worked example: Fault at a distribution transformer's secondary

Given: Infinite grid; 20 MVA, 33/11 kV transformer, Z = 10 %

Find: Fault MVA and current at the 11 kV bus.

Answer: 200 MVA, 10.5 kA

Worked example: Single line-to-ground vs three-phase

Given: E = 1 pu; Z₁ = Z₂ = j0.1 pu; Z₀ = j0.05 pu (solidly earthed); I_base = 1050 A

Find: SLG and three-phase fault currents.

Answer: SLG (12.6 kA) exceeds LLL (10.5 kA) here because Z₀ < Z₁

Common mistakes

Applications

Key takeaways

Going further