Distribution

The last mile to customers. Learn radial, ring and meshed networks, feeders and distributors, LV earthing systems, voltage-drop calculations, diversity and demand factors, and how distribution transformers are sized.

Distribution networks take power from substations at 11–33 kV and deliver it to homes, shops and factories at 400/230 V. There are far more kilometres of distribution cable than transmission line, and most customer outages originate here.

Designing distribution is about voltage drop, cable sizing, transformer sizing using realistic (diversified) demand, earthing for safety, and network configuration for reliability.

An analogy

If transmission is the motorway, distribution is the network of local roads and driveways — slower, far more numerous, and where most of the everyday traffic problems happen.

Network structures

How feeders are arranged decides reliability.

Voltage levels and limits

Customers must receive voltage within a band (e.g. 230 V +10 %/−6 % in the UK, ±10 % in many countries). Designers budget voltage drop between the MV network, the transformer, the LV feeder and the customer's own wiring.

Diversity and demand factors

Not every appliance runs at once, and not every house peaks at the same time. Demand factor converts connected load to one customer's maximum demand; diversity factor accounts for peaks not coinciding across customers. Ignoring diversity massively oversizes transformers and cables.

LV earthing systems

The earthing arrangement decides how fault current returns and how people are protected.

Automation and DER

Smart distribution uses reclosers, sectionalisers and automated switches for FLISR (fault location, isolation and service restoration) within seconds. Rooftop solar causes reverse power flow and voltage rise on LV feeders, so utilities use on-load tap changers, smart-inverter volt-var control and hosting-capacity studies.

Formulas

Worked example: Voltage drop on an LV distributor

Given: 3-phase, 400 V; I = 100 A; L = 150 m; 95 mm² Al cable: 0.44 mV/A/m

Find: Voltage drop and percentage.

Answer: 6.6 V (1.65 %)

Worked example: Transformer for a housing estate

Given: 50 houses, 10 kW connected each; Demand factor 0.4; Diversity factor 2.5; pf 0.9

Find: Group maximum demand and transformer rating.

Answer: 80 kW → 100 kVA transformer

Common mistakes

Applications

Key takeaways

Going further