Inverters

Inverters convert DC into AC of controllable voltage and frequency. Learn half- and full-bridge topologies, square-wave and sinusoidal PWM, modulation index, three-phase inverters, dead time, output filters and grid-tied operation.

An inverter switches a DC source across a load in alternating directions to create AC. With pulse-width modulation, the average of the switched voltage follows a sine wave, and a filter or the load's inductance smooths it.

Solar inverters, UPS systems, motor drives, EV traction and grid batteries all rely on inverters — they are the interface between the DC world of batteries and panels and the AC world of the grid and motors.

An analogy

An inverter is like pushing a swing: you push in one direction, then the other, at just the right times. The timing (PWM) decides how smoothly and how high it swings (voltage).

The H-bridge

Four switches form an H around the load. Closing the diagonal pair S1–S4 applies +V_dc; S2–S3 applies −V_dc. Alternating them makes AC. Never close both switches in one leg — that shorts the DC supply (shoot-through).

Output waveforms

Different switching patterns trade cost against waveform quality.

Modulation index and frequency

In SPWM, a sine reference is compared with a triangle carrier. The ratio of amplitudes is the modulation index m, which scales output voltage; the reference frequency sets output frequency. Beyond m = 1 (overmodulation) output rises further but low-order harmonics appear.

Three-phase inverters and SVPWM

Six switches in three legs produce three phases. Space-vector PWM treats the eight switch states as voltage vectors and synthesises any reference vector by time-averaging neighbours. It uses the DC bus 15 % better than sine PWM — equivalent to adding third-harmonic injection.

Dead time, filters and grid-tied control

A dead time of ~0.5–2 µs between turning one switch off and the other on prevents shoot-through, but distorts the output voltage. LC or LCL filters remove switching ripple. Grid-tied inverters synchronise with a PLL and control current into the grid; grid codes add anti-islanding, fault ride-through and reactive-power support.

Formulas

Worked example: Single-phase SPWM inverter output

Given: V_dc = 400 V; Full bridge; m = 0.9

Find: Fundamental peak and RMS.

Answer: ≈ 255 V RMS — enough for 230 V AC

Worked example: Square-wave inverter from 48 V

Given: V_dc = 48 V, full bridge, square wave

Find: Fundamental RMS.

Answer: 43.2 V RMS fundamental (THD ≈ 48 %)

Common mistakes

Applications

Key takeaways