Transformers

Transformers change AC voltage and current with ~98–99 % efficiency using mutual induction. Learn the turns ratio, EMF equation, equivalent circuit, losses, efficiency, regulation, three-phase connections and testing.

A transformer is two coils wound on a shared iron core. AC in the primary creates a changing magnetic flux; that flux links the secondary and induces a voltage in it. With no moving parts it can step voltage up or down while conserving power.

Transformers are why the grid works: generators produce ~20 kV, transformers raise it to 400 kV for transmission, lower it in stages for distribution, and finally to 400/230 V at your street. Inside electronics, small and high-frequency transformers provide isolation and voltage conversion.

An analogy

A transformer is like a gearbox for electricity. A gearbox trades speed for torque; a transformer trades voltage for current. Power in ≈ power out.

Step-up and step-down

More turns on the secondary → higher secondary voltage (step-up) and lower current. Fewer turns → step-down. Power is (almost) conserved: V₁I₁ ≈ V₂I₂. Transformers only work with changing current — DC through a transformer produces no secondary voltage and just overheats the primary.

Isolation

Primary and secondary are connected only magnetically. That galvanic isolation keeps mains-referenced faults away from users — the reason phone chargers and medical equipment use transformers even when voltage conversion could be done otherwise.

Losses and efficiency

Core loss (hysteresis + eddy currents) is roughly constant whenever the transformer is energised. Copper loss (I²R) varies with the square of load. Efficiency peaks where the two are equal — distribution transformers are designed to peak around 40–60 % load because they spend most of their life there.

Equivalent circuit and tests

A real transformer is modelled as an ideal transformer plus series winding resistance and leakage reactance, and a shunt magnetising branch. The open-circuit test (rated voltage, no load) measures core loss and the magnetising branch; the short-circuit test (rated current, low voltage) measures copper loss and the series impedance.

Voltage regulation and per-unit impedance

Regulation = (V_no-load − V_full-load)/V_full-load. It depends on the per-unit impedance (typically 4–10 % for distribution units) and the load power factor. A higher impedance also limits the fault current a transformer can deliver: I_sc = I_rated / Z_pu.

Three-phase connections and inrush

Δ–Y (delta primary, star secondary) is standard for distribution: it provides a neutral, blocks triplen harmonics and introduces a 30° phase shift (vector group Dyn11). On energisation, core saturation can draw an inrush current of 8–12× rated for a few cycles, which differential protection must learn to ignore (2nd-harmonic restraint).

Formulas

Worked example: Small step-down transformer

Given: V₁ = 230 V; V₂ = 12 V; S = 60 VA

Find: Turns ratio and full-load currents.

Answer: a ≈ 19.2, I₂ = 5 A, I₁ ≈ 0.26 A

Worked example: Efficiency at full load and maximum efficiency

Given: S = 100 kVA; P_i = 1 kW; P_cu(FL) = 1.5 kW; pf = 0.8

Find: Full-load efficiency, the load for maximum efficiency and that efficiency.

Answer: η_FL = 97.0 %, η_max = 97.03 % at 81.6 kVA

Worked example: EMF equation

Given: f = 50 Hz; N = 200 turns; φ_m = 0.01 Wb

Find: RMS induced voltage.

Answer: 444 V RMS

Common mistakes

Applications

Key takeaways

Going further