Synchronous Motors
Motors that lock exactly to the supply frequency. Learn the power-angle equation, excitation and V-curves, power-factor correction with over-excited machines, starting, hunting, and why permanent-magnet synchronous motors dominate EVs.
A synchronous motor's rotor is a magnet — either a DC-excited field winding or permanent magnets — that locks onto the stator's rotating field and turns at exactly synchronous speed, whatever the load (up to its limit).
Because its excitation can be adjusted, a synchronous motor can draw leading current and correct the power factor of a whole plant. Permanent-magnet versions (PMSM) power most electric vehicles, servo drives and wind turbines.
An analogy
A synchronous motor is like a dog on a stiff leash following a walker exactly. Pull harder (more load) and the leash angle increases, but the dog keeps the same pace. Pull too hard and the leash snaps — the motor 'pulls out of step'.
Locked to the grid
The rotor field locks to the stator field, so speed = 120f/P exactly: 1500 rpm for 4 poles at 50 Hz, with no slip. That makes synchronous motors ideal for timing-critical drives, compressors running at constant speed, and clocks.
Load angle δ
As mechanical load increases, the rotor falls slightly behind the stator field by an angle δ, and power transferred grows as sin δ. At δ = 90° power peaks; any more load and the rotor slips poles and loses synchronism (pull-out).
Excitation and V-curves
For a fixed load, changing field current changes the motor's power factor. Under-excited: it draws lagging (inductive) current. Normally excited: unity pf, minimum current. Over-excited: it draws leading current and supplies reactive power to the grid, acting as a 'synchronous condenser'. Plotting armature current against field current gives the characteristic V-shaped curves.
Starting and hunting
A synchronous motor has zero average torque at standstill, so it isn't self-starting. It is started as an induction motor using damper (amortisseur) bars in the rotor, then the DC field is applied near synchronous speed. The same damper bars suppress 'hunting' — oscillations of δ after load changes.
PMSM and field-oriented control
Permanent-magnet synchronous motors need no field current, so they have no rotor copper loss and very high efficiency and power density. Driven by an inverter with rotor-position feedback and field-oriented control, they give precise torque from zero speed — the standard for EV traction, robotics and servo systems.
Formulas
- Speed:
N = N_s = 120 f / P (exactly) - Power–angle equation (3-phase):
P = 3 · V·E·sin δ / X_s - Pull-out power:
P_max = 3·V·E / X_s (δ = 90°) - Torque:
T = P / ω_s
Worked example: Power at a given load angle
Given: V_LL = 400 V → V_ph = 231 V; E = 250 V/phase; X_s = 5 Ω; δ = 20°
Find: Power delivered and the pull-out power.
- P = 3 × 231 × 250 × sin 20° / 5
- = 3 × 11 550 × 0.342 = 11.85 kW
- P_max = 3 × 231 × 250 / 5 = 34.65 kW
Answer: 11.9 kW at δ = 20°, pull-out at 34.7 kW
Worked example: Synchronous speed
Given: 6 poles; f = 50 Hz
Find: Running speed.
- N = 120 × 50 / 6 = 1000 rpm (exactly, at any load below pull-out)
Answer: 1000 rpm
Common mistakes
- Wrong: Applying DC field current at standstill to start the motor. — Right: Start it asynchronously (damper bars or a VFD) and apply excitation close to synchronous speed.
- Wrong: Operating near δ = 90° to get the most power. — Right: Keep δ around 20–35° to leave margin for transient load and voltage dips.
Applications
- Power-factor correction: Large plants run over-excited synchronous motors on compressors so they also cancel the reactive power of induction motors.
- EV traction: Interior-permanent-magnet synchronous motors deliver high torque density and efficiency above 95 % across a wide speed range.
- Grid support: Synchronous condensers (motors with no mechanical load) are being installed again to supply inertia and short-circuit strength to renewable-heavy grids.
Key takeaways
- Speed = 120f/P exactly; no slip.
- P = 3VE sin δ / X_s; pull-out at δ = 90°.
- Excitation controls power factor (V-curves); over-excited = leading.
- Not self-starting; PMSMs with FOC dominate EVs and servos.
Going further
- Salient-pole machines: With non-uniform air gaps (salient poles), a reluctance torque term adds to the excitation torque: P = VE sin δ/X_d + V²(1/X_q − 1/X_d) sin 2δ/2. Interior-PM EV motors exploit this reluctance torque for extra torque and field weakening.
- Transient stability: After a fault, the rotor angle swings. The equal-area criterion decides whether the machine regains synchronism: the accelerating area during the fault must be matched by a decelerating area before δ reaches its unstable limit.
- Synchronous reluctance motors: SynRM rotors have no magnets and no windings, only shaped iron flux barriers. Paired with a VFD they reach IE4/IE5 efficiency without rare earths.