HVAC & Indoor Environmental Quality
Keeping buildings comfortable and healthy. Learn thermal comfort (PMV, adaptive comfort, ASHRAE 55/IMAC), psychrometrics (dry bulb, humidity, enthalpy), cooling load components (envelope, glazing, people, lighting, equipment, ventilation), sizing in TR, HVAC systems (split, VRF, chilled water with AHUs/FCUs, district cooling), ventilation rates and IAQ (CO₂, PM2.5), energy efficiency (COP, IKW/TR, economisers, heat recovery), and passive/mixed-mode design — with Python for an office cooling load and fresh-air rate.
HVAC (heating, ventilation and air conditioning) is typically the largest energy user in commercial buildings in India — 40–60% of electricity. Correct load estimation and system selection matter for comfort, cost and emissions.
Indoor air quality is equally important: adequate fresh air and filtration protect health and productivity.
An analogy
A building's cooling load is like a leaking bucket you must keep empty: heat pours in through walls, windows, people and equipment, and the air conditioner must pump it out as fast as it enters.
Thermal comfort
Comfort depends on air temperature, radiant temperature, humidity, air speed, clothing and activity. Typical AC setpoints: 24–26 °C, 50–60% RH (BEE recommends 24 °C default). Adaptive comfort (IMAC for India) shows people in naturally ventilated buildings accept wider ranges; ceiling fans extend comfort by 2–3 °C.
Psychrometrics and loads
Moist air properties (dry bulb, wet bulb, dew point, humidity ratio, enthalpy) are read from the psychrometric chart. Cooling loads are sensible (temperature) and latent (moisture from people, fresh air). Peak loads are calculated hour-by-hour (CLTD/RTS methods or simulation) because solar gains peak at different times on different façades.
HVAC systems
Common systems:
- Split and packaged units — small spaces
- VRF/VRV — multiple indoor units, variable refrigerant flow, mid-size buildings
- Chilled water — chillers (screw/centrifugal, water- or air-cooled), cooling towers, AHUs/FCUs, pumps
- Dedicated outdoor air systems (DOAS) with energy recovery
- District cooling, thermal storage, radiant cooling, evaporative cooling in dry climates
IAQ and efficiency
Ventilation per ASHRAE 62.1/NBC (e.g. ~10 L/s/person in offices); CO₂ below ~1000 ppm indicates adequate ventilation; MERV 13+ filtration for PM2.5, UV-C and demand-controlled ventilation. Efficiency measures: high-COP chillers (0.55–0.65 kW/TR), VFDs on pumps/fans, economisers, heat recovery, higher chilled-water temperatures, BMS optimisation and continuous commissioning.
Formulas
- Sensible load:
Q_s = 1.2·V̇·ΔT (kW, V̇ in m³/s) - Total (enthalpy) load:
Q = ρ·V̇·Δh - Glazing solar:
Q = A·SHGC·I - Air changes:
ACH = V̇(m³/h)/room volume - Chiller efficiency:
kW/TR = 3.517/COP
Worked example: Sensible load of supply air
Given: 2 m³/s air, ΔT 10 K
Find: Q_s.
- 1.2 × 2 × 10
Answer: 24 kW
Worked example: ACH
Given: 1800 m³/h fresh air, room 2000 m³
Find: ACH.
- 1800/2000
Answer: 0.9 ACH
Worked example: Chiller power
Given: 300 TR at 0.6 kW/TR
Find: Power.
- 300 × 0.6
Answer: 180 kW
Office cooling load and fresh air
# Cooling load estimate for an office floor and ventilation
area, people = 500.0, 50
Q_env = 500 * 0.9 * 12 / 1000 # kW: wall/roof UA ~0.9 W/m2K per m2 floor * 12 K
Q_glass = 120 * 0.35 * 450 / 1000 # 120 m2 glass, SHGC 0.35, 450 W/m2 solar
Q_people = people * (75 + 55) / 1000 # sensible + latent W per person
Q_light = area * 8 / 1000 # 8 W/m2 LED
Q_equip = area * 12 / 1000 # 12 W/m2 plug loads
fresh = people * 10 / 1000 # 10 L/s per person -> m3/s
Q_vent = 1.2 * fresh * (60 - 45) # kW via enthalpy difference kJ/kg (outdoor 60, indoor 45)
total = Q_env + Q_glass + Q_people + Q_light + Q_equip + Q_vent
for name, q in (("envelope", Q_env), ("glazing solar", Q_glass), ("people", Q_people), ("lighting", Q_light), ("equipment", Q_equip), ("fresh air", Q_vent)):
print(f"{name:14s} {q:5.1f} kW")
print(f"total {total:.1f} kW = {total/3.517:.1f} TR ({area/(total/3.517):.0f} m2 per TR)")
print(f"fresh air {fresh*1000:.0f} L/s = {fresh*3600:.0f} m3/h")
# envelope 5.4 kW
# glazing solar 18.9 kW
# people 6.5 kW
# lighting 4.0 kW
# equipment 6.0 kW
# fresh air 9.0 kW
# total 49.8 kW = 14.2 TR (35 m2 per TR)
# fresh air 500 L/s = 1800 m3/hSolar gain through glazing is the largest single load (38%) — façade design matters more than anything else. Fresh air adds 9 kW because humid outdoor air must be cooled and dehumidified; energy-recovery wheels can recover much of this. 35 m²/TR is a typical efficient office (old rules of thumb of 15–20 m²/TR lead to oversizing).
Common mistakes
- Wrong: Sizing by m²/TR rules of thumb. — Right: Calculate loads by component and hour.
- Wrong: Setting AC at 18–20 °C. — Right: 24–26 °C with fans saves 20–30%.
- Wrong: Cutting fresh air to save energy. — Right: Use heat recovery and DCV instead — IAQ matters.
Applications
- Offices & malls: Chilled-water plants with BMS.
- Hospitals: Operating theatre air changes and HEPA.
- Data centres: Precision cooling and hot/cold aisles.
- Homes: Inverter ACs and ceiling fans.
Key takeaways
- Loads: envelope, glazing, people, lights, equipment, fresh air.
- 1 TR = 3.517 kW; avoid rule-of-thumb oversizing.
- Choose systems by scale; use VFDs and recovery.
- Comfort and IAQ matter as much as energy.
Going further
- Radiant cooling: Chilled slabs and panels with DOAS.
- Thermal energy storage: Ice/chilled water for peak shifting.
- Fault detection & diagnostics: Analytics on BMS data.